Permit Number: T14CM05356
Parcel: 137055310

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM05356
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/04/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
09/04/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed .
09/04/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The Mechanical Compliance Certificate was not included in this submittal. [Initial comment: Provide the Mechanical Compliance Certificate to demonstrate that the new HVAC equipment complies with the 2012 International Energy Code.]
2. The minimum size for a condensate drain is ¾". Reference: Section 307.2.2, IMC 2012. [Initial comment: Show the size, routing, and termination of the condensate drains. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson.]
09/08/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved