Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM05356
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/04/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 09/04/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | . |
| 09/04/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The Mechanical Compliance Certificate was not included in this submittal. [Initial comment: Provide the Mechanical Compliance Certificate to demonstrate that the new HVAC equipment complies with the 2012 International Energy Code.] 2. The minimum size for a condensate drain is ¾". Reference: Section 307.2.2, IMC 2012. [Initial comment: Show the size, routing, and termination of the condensate drains. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson.] |
| 09/08/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |