Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM05279
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/25/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Panel A shown as existing 150A MLO panel. Your calculated demand on this panel is shown as 197 amps. My rough calculation has a load of slightly more than 200 Amps. Either way you are overloading your panel. If you want to use switch for exhaust fan it needs to be a programmable time in order to comply with mechanical code anti-recirculation requirements. |
| 08/25/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | All air supplied to a restroom shall be exhausted (i.e. exhaust at least the same amount of air that is supplied to the restroom). Reference: Section 403.2, IMC 2012. |
| 08/25/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson. |
| 08/25/2014 | ROBERT SHERRY | WATER | REVIEW | Completed |