Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T14CM05279
Parcel: 113071480

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM05279
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Reqs Change Panel A shown as existing 150A MLO panel. Your calculated demand on this panel is shown as 197 amps. My rough calculation has a load of slightly more than 200 Amps. Either way you are overloading your panel.

If you want to use switch for exhaust fan it needs to be a programmable time in order to comply with mechanical code anti-recirculation requirements.
08/25/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change All air supplied to a restroom shall be exhausted (i.e. exhaust at least the same amount of air that is supplied to the restroom). Reference: Section 403.2, IMC 2012.
08/25/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson.
08/25/2014 ROBERT SHERRY WATER REVIEW Completed