Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM05279
Parcel: 113071480

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM05279
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/14/2014 STEVE SHIELDS ZONING REVIEW Approved
08/15/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1.Provide a mechanical plan. Show the location of the thermostat controlling this suite.
2. Show that the new restroom will be mechanically exhausted (i.e. there can be no return air from a restroom).
08/15/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1) Show circuiting for required restroom exhaust

2) Clarify where electrical panels are. Show how separating out this suite will maintain compliance with NEC 24.24.
08/15/2014 ROBERT SHERRY WATER REVIEW Reqs Change Verify that the fixtures noted in the plumbing fixture schedule represent the total demand served by the existing water meter. (Note that a tank-type water closet has 5 WFU and a flush-valve water closet has 10 WFU.)
08/15/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/15/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Specify the piping materials to be employed in this activity. Reference: Section 107.2.1, IBC 2012.
2. Provide fixture descriptions for all plumbing fixtures. Reference: Section 402, IPC 2012 and Section 107.2.1, IBC 2012.
3. Show the source of the hot water supply. Reference: Section 107.2.1, IBC 2012.
4. Show how the temperature of the hot water supply to the public lavatory is controlled. Reference: Sections 416.5 and 607.1, IPC 2012 and Section C404.3, IECC 2012.
5. Clarify the "extra" keynote #10 (next to keynote #8).
08/15/2014 CARL SCHULTZ FIRE REVIEW Approved
08/15/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/20/2014 CPIERCE1 WWM REVIEW Completed
08/20/2014 LOREN MAKUS ENGINEERING REVIEW Approved