Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM05272
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/15/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Verify that the use of a temperature mixing valve with the tankless water heater complies with the water heater manufacturer's listing requirements. Reference: Section 303.2, IPC 2012. 2. Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2012, for an A-2 occupany of 30 people. |
08/15/2014 | ROBERT SHERRY | WATER | REVIEW | Completed | |
08/15/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012. 2. Provide ventilation calculations based on the architect's assumed building use. |
08/18/2014 | CPIERCE1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
08/18/2014 | CPIERCE1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
08/18/2014 | CPIERCE1 | WWM | REVIEW | Needs Review | |
08/18/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed |