Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM05272
Parcel: 11901076B

Address:
3312 S 6TH AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM05272
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify that the use of a temperature mixing valve with the tankless water heater complies with the water heater manufacturer's listing requirements. Reference: Section 303.2, IPC 2012.
2. Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2012, for an A-2 occupany of 30 people.
08/15/2014 ROBERT SHERRY WATER REVIEW Completed
08/15/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.
2. Provide ventilation calculations based on the architect's assumed building use.
08/18/2014 CPIERCE1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
08/18/2014 CPIERCE1 BUILDING-COMMERCIAL REVIEW Needs Review
08/18/2014 CPIERCE1 WWM REVIEW Needs Review
08/18/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed