Permit Number: T14CM05240
Parcel: 10309068D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM05240
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/13/2014 STEVE SHIELDS ZONING REVIEW Approved
08/13/2014 LOREN MAKUS ENGINEERING REVIEW Approved
08/14/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
08/14/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide the heating/cooling calculations for the new heat pump.
08/14/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A3; DETAILS 1 AND 2: THE IBC SECTION 1607.14 REQUIRES INTERIOR PARTITIONS TO BE CAPABLE OF RESISTING A MINIMUM HORIZONTAL LOAD OF 5 P.S.F. DO THE INDICATED DIAGONAL STUD BRACES AT PARTITION CORNERS MEET THAT CRITERIA? VERIFY. INDICATE THE BRACING SIZE AND CONNECTIONS ON THE DETAILS.
08/14/2014 ROBERT SHERRY WATER REVIEW Completed
08/14/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/14/2014 CARL SCHULTZ FIRE REVIEW Approved
08/14/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/19/2014 AROMERO4 WWM REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/19/2014 AROMERO4 APPROVAL SHELF Completed
08/19/2014 AROMERO4 OUT TO CUSTOMER Completed
08/19/2014 AROMERO4 REJECT SHELF Completed