Permit Number: T14CM05238
Parcel: 13419042D

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM05238
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/05/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/08/2014 ROBERT SHERRY WATER REVIEW Reqs Change Comment not addressed. [Initial comment: Provide the size of the water meter serving this building and the total demand it will serve when the proposed fixtures are installed. Reference: Section 107.2.1, IBC 2012.]
09/08/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Comment not addressed (no cut sheets have been provided for the owner's equipment and fixtures). [Initial comment: Provide material standards for all plumbing fixtures being provided by others (e.g. NSF listed). Reference: Sections 303.4 and 402, IPC 2012.]
09/08/2014 KEN BROUILLETTE FIRE REVIEW Approved
09/08/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the termination point for the machinery room ventilation fans EF-1 and EF-6 per Section 1105.6.1, IMC 2012 (i.e. not less than 20 feet from any opening into the building. [Initial comment: Provide a design for the specified compressor room ventilation system that complies with Section 1105, IMC 2012.]