Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T14CM05238
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/05/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/08/2014 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Comment not addressed. [Initial comment: Provide the size of the water meter serving this building and the total demand it will serve when the proposed fixtures are installed. Reference: Section 107.2.1, IBC 2012.] |
| 09/08/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Comment not addressed (no cut sheets have been provided for the owner's equipment and fixtures). [Initial comment: Provide material standards for all plumbing fixtures being provided by others (e.g. NSF listed). Reference: Sections 303.4 and 402, IPC 2012.] |
| 09/08/2014 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 09/08/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the termination point for the machinery room ventilation fans EF-1 and EF-6 per Section 1105.6.1, IMC 2012 (i.e. not less than 20 feet from any opening into the building. [Initial comment: Provide a design for the specified compressor room ventilation system that complies with Section 1105, IMC 2012.] |