Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T14CM05238
Parcel: 13419042D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM05238
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/18/2014 KEN BROUILLETTE FIRE REVIEW Denied FIRE REVIEW:
1. THE CODE ANALYSIS INDICATES VB CONSTRUCTION AND UNLIMITED AREA. THIS IS NOT ACCEPTABLE PER THE IBC
2. THE EXIT THROUGH THE STOCK ROOM IS NOT APPROVED AS DESIGNED. PLEASE REVISE EXITING PLAN TO MEET CODE.
08/21/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET G1; CODE PLAN KEYNOTES: NOTE 4 INDICATES ONE EXIT IF OCCUPANCY DOES NOT EXCEED 29. REVISE THAT TO 49.
2. SHEET A4 (PARTITION TYPE); SHEET A14 (DETAILS 1, 2, AND 3): PROVIDE A NOTE ON SHEET A4 TO REFERENCE DETAILS 1, 2, AND 3 FOR PARTITION BRACING. INDICATE ON EACH PARTITION TYPE WHICH BRACING TYPE IS REQUIRED (USE NOTES 10 AND 11 ON THE REFLECTED CEILING NOTES ON SHEET A7).
3. SHEET A5; FLOOR PLAN NOTES: NOTE 8 INDICATES TO SEE SHEET A4 FOR PARTITION TYPES. THOSE PARTITION TYPES ARE ALSO ON SHEET A5.
4. SHEET A18; SECTION 7: A DIMENSION FROM THE WALL TO THE SIGNAGE PLATE INDICATES 'DEPTH PER UPPER LEVEL PLAN-1 1/16" '. EXPLAIN THIS.
5. SHEET A19; ENLARGED DEMONSTRATION KITCHEN PLAN: PER THE IBC SECTION 1109, SINKS AND KITCHENS IN ACCESSIBLE SPACES SHALL BE ACCESSIBLE. THIS WOULD LOWER THE COUNTER TOPS TO 34" ABOVE FINISH FLOOR. VERIFY.
6. SHEET S1.0: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE GENERAL NOTES.
7. SHEET S3.0; DETAIL 303: PROVIDE THE LATERAL BRACING SIZE AND CONNECTION (SIZE AND QUANTITY) TO THE STUD HANGER AND THE ROOF STRUCTURE ABOVE.
8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
08/22/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
08/26/2014 ROBERT SHERRY WATER REVIEW Reqs Change Provide the size of the water meter serving this building and the total demand it will serve when the proposed fixtures are installed. Reference: Section 107.2.1, IBC 2012.
08/26/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide material standards for all plumbing fixtures being provided by others (e.g. NSF listed). Reference: Sections 303.4 and 402, IPC 2012.
2. Appliances (e.g. ice makers, coffee makers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012.
3. Provide separate indirect waste pipes for each food-handling fixture to protect against cross-contamination or fouling (e.g. for each compartment of a 3-compartment sink). Reference: Section 801.2, IPC 2012.
4. Indirect waste receptors shall not be installed in a closet or cupboard, or unventilated space. Indirect waste receptors shall have ready access. Reference: Sections 202 and 802.3, IPC 2012.
08/28/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the font size used on the drawings to a minimum height of 3/32-inch. Reference: Section 107.2.1, IBC 2012.
2. Provide the operating capacity of each of the refrigerant systems, including the type and amount of the refrigerant used in each independent refrigerant circuit. Reference: Sections 1101.1, 1103.1, IMC 2012.
3. Provide a design for the specified compressor room ventilation system that complies with Section 1105, IMC 2012.
4. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project (i.e. RTU-6). Reference: Sections C403.2.1 and C403.2.2, IECC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/29/2014 AROMERO4 APPROVAL SHELF Completed
08/29/2014 AROMERO4 OUT TO CUSTOMER Completed
08/29/2014 CPIERCE1 REJECT SHELF Completed