Permit Number: T14CM05025
Parcel: 14111027B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM05025
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/10/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT 4; SHEET S1.1; STRUCTURAL NOTES: REMOVE NOTE 7.
2. PREVIOUS COMMENT 5; GENERAL: PROVIDE TWO SETS OF STRUCTURAL CALCULATIONS FOR EACH CANOPY DESIGN.
3. PREVIOUS COMMENT 6; GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/11/2014 KROBLES1 APPROVAL SHELF Completed
12/11/2014 KROBLES1 OUT TO CUSTOMER Completed
12/11/2014 CPIERCE1 REJECT SHELF Completed