Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T14CM05025
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/15/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET C1 (SITE PLAN); SHEET S1.1 (ROOF FRAMING PLAN): CANOPIES ONE AND TWO INDICATE 2880 SF EACH ON THE SITE PLAN, WHILE SHEET S1.1 INDICATES EACH CANOPY IS 30' X 72' (2160 SF). CLARIFY. 2. SHEET C2 (SITE PLAN); SHEET S1.1 (ROOF FRAMING PLAN): THE SITE PLAN INDICATES CANOPIES ONE AND TWO ARE 30' WIDE, WHILE THE ROOF FRAMING PLAN INDICATES A WIDTH GREATER THAN 30' PER THE DIMENSION LINE. CLARIFY. 3. SHEET C2 (SITE PLAN); SHEET S1.1 (ROOF FRAMING PLAN): THE SITE PLAN INDICATES CANOPY FOUR IS 40' WIDE, AND THE STRUCTURAL CALCULATIONS PROVIDE A DESIGN FOR THE 40' WIDE CANOPY. HOWEVER, THE STRUCTURAL DRAWINGS SHOW A DIMENSIONED PLAN ONLY FOR THE 30' WIDE CANOPY. PROVIDE THE 40' WIDE CANOPY PLAN AND DETAILS ON THE DRAWINGS. 4. SHEET S1.1; STRUCTURAL NOTES: REMOVE NOTE 7. 5. GENERAL: PROVIDE TWO SETS OF STRUCTURAL CALCULATIONS FOR EACH CANOPY DESIGN. 6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/03/2014 | CPIERCE1 | REJECT SHELF | Completed |