Permit Number: T14CM04983
Parcel: 130083440

Address:
3456 E 27TH ST

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T14CM04983
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/09/2014 STEVE SHIELDS ZONING REVIEW Denied CDRC TRANSMITTAL

FROM: Steve Shields, Lead Planner


PROJECT:
3456 E. 27th Street
Permit ramada in front yard
T14CM04983


TRANSMITTAL: September 9, 2014


COMMENTS: The following comments are for the purpose of applying for a variance before the Board of Adjustment (UDC Section 3.10.1).

This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). Based on a wall height of 7'-0" the required perimeter yard setback from the proposed ramada to the east property line is 6'-0", proposed setback is 3'-10"

The minimum setback to the front street perimeter property line is the greater of twenty (20) feet, or one and one-half (1 ½) the height of the proposed wall (UDC 6.4.5.C.1.a). Based on a wall height of 8'-0" the required perimeter yard setback from the proposed ramada to the street perimeter yard property line is 20'-0", proposed setback is 3'-10"

Per UDC Section 6.6.3.B Detached accessory buildings are not permitted in the buildable area extending the full width of the lot between the principal building and the front street lot line, except for terraces and steps not over three feet high above the natural grade, paved areas, and fences or walls. Proposed ramada, detached accessory strucuture, is located within the buildable area extending the full width of the lot between the principal building and the front street lot line.
09/16/2014 SPOWELL1 ENGINEERING REVIEW Needs Review
09/16/2014 SPOWELL1 BUILDING-RESIDENTIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/16/2014 SHANAE POWELL OUT TO CUSTOMER Completed