Permit Number: T14CM04952
Parcel: 13315346A

Address:
1849 N KOLB RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM04952
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2014 MICHAEL ST. PAUL ZONING REVIEW Approved
08/04/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide cooling/heating load calculations for the new heat pump.
2. Revise the ventilation calculations using the current code (2012 IMC). Use a "lecture classroom" as the ocupancy type.
3. Clarify the sequence of operation for the new heat pump. No economizer is specified for the unit but the sequence of operation calls for an economizer.
08/04/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
08/04/2014 ROBERT SHERRY WATER REVIEW Reqs Change Show the location of the backflow preventer and the water meter on the drawing.
08/04/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/04/2014 LHANLY1 WWM REVIEW Passed
08/04/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Replot drawing to show all of the plumbing features.
08/04/2014 JASON GREEN ENGINEERING REVIEW Approved
08/04/2014 KEN BROUILLETTE FIRE REVIEW Approved
08/04/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed