Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM04952
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/04/2014 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 08/04/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide cooling/heating load calculations for the new heat pump. 2. Revise the ventilation calculations using the current code (2012 IMC). Use a "lecture classroom" as the ocupancy type. 3. Clarify the sequence of operation for the new heat pump. No economizer is specified for the unit but the sequence of operation calls for an economizer. |
| 08/04/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 08/04/2014 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Show the location of the backflow preventer and the water meter on the drawing. |
| 08/04/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/04/2014 | LHANLY1 | WWM | REVIEW | Passed | |
| 08/04/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Replot drawing to show all of the plumbing features. |
| 08/04/2014 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 08/04/2014 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 08/04/2014 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |