04/27/2015 MICHAEL ST. PAUL ZONING REVIEW Reqs Change P&DS TRANSMITTAL


FROM: Michael St.Paul, Planning Technician

PROJECT:
T14CM04933
632 South Curtis Avenue
Garage addition to SFR


TRANSMITTAL: April 27, 2015


COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).


This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). The height of the proposed garage addition is twenty-one (21) feet. The required setback to the west property line is fourteen (14) feet. The proposed setback is three (3) feet to the west property line.
04/27/2015 MICHAEL ST. PAUL NPPO REVIEW Passed