Permit Review Detail
Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T14CM04846
Review Name: WALK THRU - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/30/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A0; BUIILDING CODE DATA: REVISE THE 'CURRENT ADA' TO THE 2009 EDITION OF THE ICC/ANSI A117.1. 2. SHEET A1; KEYED NOTES: NOTES 7, 9, 11, 14, 16, AND 17 WERE NOT LOCATED ON THE ELEVATIONS. VERIFY. 3. SHEET A1; KEYED NOTES: NOTE 10 DOES NOT APPEAR TO BE SHOWN IN THE CORRECT LOCATIONS ON THE ELEVATIONS. VERIFY. 4. SHEET A1; KEYED NOTES: NOTE 12 DOES NOT APPEAR TO BE SHOWN IN THE CORRECT LOCATION ON ELEVATION 2. VERIFY. 5. SHEET A1; KEYED NOTES: NOTE 13 DOES NOT APPEAR TO BE SHOWN IN THE CORRECT LOCATION ON ELEVATION 2. VERIFY. 6. SHEET A1; KEYED NOTES: NOTE 12 DOES NOT APPEAR TO BE SHOWN IN THE CORRECT LOCATION ON ELEVATION 2. VERIFY. 7. SHEET A1; KEYED NOTES: NOTE 21 DOES NOT APPEAR TO BE SHOWN IN THE CORRECT LOCATION ON ELEVATION 2. VERIFY. 8. SHEET A1; KEYED NOTES: NOTE 22 DOES NOT APPEAR TO BE SHOWN IN THE CORRECT LOCATION ON ELEVATION 2. VERIFY. 9. SHEET A1; KEYED NOTES: NOTES 24, 25, AND 26 ARE SHOWN AT THE ELEVATIONS, BUT NOT LISTED IN THE KEYED NOTES. PROVIDE. 10. GENERAL: PROVIDE STRUCTURAL CALCULATIONS TO CONFIRM THE EXISTING ROOF STRUCTURE CAN SUPPORT THE NEW HOOD AND ADDITIONAL LOADS. 11. GENERAL: PROVIDE DETAILS FOR HANGING THE NEW HOOD FROM THE EXISTING ROOF STRUCTURE. 12. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 07/30/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the submittal to show the complete scope of work and how the new work relates to the existing conditions. Include: 1. the gas piping system modifications 2. show how the hood is mounted to the building (with structural calculations) 3. clarify the ceiling assembly (is it rated?) 4. clarify the exhaust flow rate - 4 values are given 5. provide the listing information for the ceiling penetration detail 6. coordinate the keynotes with the drawing 7. show where the hood will be located in the suite 8. Provide specifications for the exhaust fan and the makeup air unit 9.verify if any electrical changes will be required |