Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM04765
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/30/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/04/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | SHEET A3 1. Provide drinking fountains as per 2012 IBC Section 1109.5 and ICC A117.1, Section 602. 2. Recalculate your occupancy load providing occupancy in the 300 s.f. entry lobby and the open entry foyer using an occupancy ration of 1 to 5. a. Reconfirm with the fire marshall the need for a sprinkler system with the newly calculated load which will probably exceed the 300 occupant load required for sprinklers as per Section 903.2.1.3. 3. The third door in the lower vestible between the dwelling units and mediation room does not have a number and does not meet clearances as required by ICC A117.1, Section 404.2.3.2, figure (a). 4. A fire wall is required between the residential dwelling portion of the facility and the mediation room as per Table 508.4. Two hours if non sprinklered and 1 hour if sprinklered. SHEET S3.0 5. Calcs page 6, DJ4 for new kitchen exhaust hood support is not shown on the key plan nor the roof framing plan. END OF REVIEW |
| 08/08/2014 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: 5326 E. Pima Street T14CM04765 Building Plan (1st Review) TRANSMITTAL DATE: August 8, 2014 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. If the development package sheets are going to be part of the building submittal they will need to be the signed approved set or marked as reference only. 3. Zoning has reviewed the building plans but cannot approve until a development package has been approved. 4. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 08/14/2014 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 08/15/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide sufficient detail on the drawings to evaluate the energy compliance of the additions to the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. The information on the drawings shall agree with the component descriptions shown on the envelope compliance certificate. Note that the residential occupancy areas of the building addition are to meet the residential provisions of the IECC while the commercial occupancies are to meet the commercial provisions of the IECC. Reference: Sections C101.4.3, C101.4.6, C101.5, and C103.2, International Energy Conservation Code 2012. 2. Relocation of the existing rooftop air conditioner AC-3 to handle new loads constitutes new work. Show that the unit meets the requirements of the current codes. Reference: Section 101.4.3, IECC 2012. 3. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012. 4. Details 12/D2 and 13/D2 show a roof access ladder. Where does this ladder occur? Provide dimensions for the ladder that comply with Section 306.5, IMC 2012. Reference: Section 107.2.1, IBC 2012. 5. Exhaust fans EF-2 and EF-3 have separate wall switches but are required to run continuously during occupied hours. Provide a method for controlling the operation of the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2012. 6. Revise the ventilation calculations to indicate the occupancy classifications that were used to determine the required ventilation rates for each space. Reference: Section 403.2, IMC 2012. 7. Residential occupancies require mechanical ventilation. Reference: Section R403.5, IECC 2012. 8. Revise the ventilation calculations to show the two new bedrooms being served by the ductless heat pumps, not AC-3. Show how they are to be supplied with outside air. Reference: Section 403.2, IMC 2012 and Section R403.5, IECC 2012. 9. If a "comfort balance" is performed after the diffusers have been balanced to the air flows shown on the HVAC drawings, explain how the proper amount of outside air to each space will be assured. Reference: Section 403.7, IMC 2012. 10. Provide an exhaust fan rated for use with a Type I hood. Reference: Section 506.5.1, IMC 2012. |
| 08/15/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Coordinate the architectural plans with the plumbing plans; A2 shows an additional floor sink located to the south of the 3-compartment sink that is not shown on the plumbing plans. Reference: Section 107.2.1, IBC 2012. 2. Clarify keynotes 7, 8, and 9 on sheet P2. Reference: Section 107.2.1, IBC 2012. 3. Provide the number of drinking fountains that complies with the requirements of Section 1109.5.1, IBC 2012 and Section 410.2, IPC 2012. 4. Verify that the use of a temperature mixing valve with a tankless water heater (WH-3) complies with the water heater manufacturer's listing requirements. Reference: Section 303.2, IPC 2012. 5. The temperature mixing valve specified for P-1 is listed as conforming to ASSE 1070, not ASSE 1016. Revise the specifications to note the correct ASSE standard so that an incorrect mixing valve is not substituted. Reference: Sections 416.5 and 607.1.2, IPC 2012. 6. According to sheet P2, the hot water supply piping to the existing four lavatories is being replaced. Show how the temperature of the hot water supply to these public lavatories is to be controlled. Reference: Sections 416.5 and 607.1, IPC 2012 and Section C404.3, IECC 2012. 7. Provide a vent downstream of the hydromechanical grease interceptor to protect the seal for the grease interceptor. Reference: Section 1003.9, IPC 2012. 8. The specified hydromechanical grease interceptor (Rockford RP-75) requires the installation of an external flow control device. Show how this device is to be installed. Reference: Sections 303.2 and 1003.3.4.2, IPC 2012. 9. Clarify the dimensions of the primary scupper opening shown in details 14/D2 and 19/D2. Clarify the location of the overflow opening in the leader box shown in Details 15/D2 and 19/D2. Reference: Section 107.2.1, IBC 2012. |
| 08/19/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed |