Permit Number: T14CM04729
Parcel: 13215024A

Address:
3690 S PARK AV

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T14CM04729
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT 5; SHEET A1.1; WALL TYPES SCHEDULE: WALL TYPE E STILL DOES NOT INDICATE THE GYPSUM BOARD AND STUDS AT THE PHARMACY ARE UP TO THE UNDERSIDE OF THE EXISTING DECK. PLEASE REVISE.
2. SHEET A1.1; FLOOR PLAN: THE OPENING IN THE NORTH WALL OF THE CHECK IN ROOM (KEYNOTE 19) MUST HAVE A ONE HOUR RATED ASSEMBLY.
3. SHEET A1.1; FLOOR PLAN: THE WALL TYPE I OVER THE OPENING IN THE NORTH WALL OF THE CHECK IN ROOM MUST EXTEND TO THE UNDERSIDE OF THE EXISTING DECK. REVISE WALL TYPE I TO READ: 'AT PHARMACY AND CHECK IN ROOM LOCATIONS, STUDS AND GWB UP TO UNDERSIDE OF DECK'.
4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/26/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Multiple flexible ducts are penetrating a fire-rated partition (wall type U, room 133) without fire dampers. Reference: Section 714.3.1, IBC 2012.
2. Clarify how the ducts penetrating the roof near room 166 are negotiating the fire-rated partition that extends to the roof deck (wall type L).
3. A flexible duct is penetrating a fire-rated partition (wall type L) over door 146A (between rooms 100 and 146). Reference: Section 714.3.1, IBC 2012.
4. Two flexible ducts connecting transfer grilles may be penetrating an existing fire-rated partition (wall type M); how high does the partition extend?

Final Status

Task End Date Reviewer's Name Type of Review Description
06/02/2015 FERNE RODRIGUEZ OUT TO CUSTOMER Completed