Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T14CM04729
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/19/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. PREVIOUS COMMENT 5; SHEET A1.1; WALL TYPES SCHEDULE: WALL TYPE E STILL DOES NOT INDICATE THE GYPSUM BOARD AND STUDS AT THE PHARMACY ARE UP TO THE UNDERSIDE OF THE EXISTING DECK. PLEASE REVISE. 2. SHEET A1.1; FLOOR PLAN: THE OPENING IN THE NORTH WALL OF THE CHECK IN ROOM (KEYNOTE 19) MUST HAVE A ONE HOUR RATED ASSEMBLY. 3. SHEET A1.1; FLOOR PLAN: THE WALL TYPE I OVER THE OPENING IN THE NORTH WALL OF THE CHECK IN ROOM MUST EXTEND TO THE UNDERSIDE OF THE EXISTING DECK. REVISE WALL TYPE I TO READ: 'AT PHARMACY AND CHECK IN ROOM LOCATIONS, STUDS AND GWB UP TO UNDERSIDE OF DECK'. 4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
05/26/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Multiple flexible ducts are penetrating a fire-rated partition (wall type U, room 133) without fire dampers. Reference: Section 714.3.1, IBC 2012. 2. Clarify how the ducts penetrating the roof near room 166 are negotiating the fire-rated partition that extends to the roof deck (wall type L). 3. A flexible duct is penetrating a fire-rated partition (wall type L) over door 146A (between rooms 100 and 146). Reference: Section 714.3.1, IBC 2012. 4. Two flexible ducts connecting transfer grilles may be penetrating an existing fire-rated partition (wall type M); how high does the partition extend? |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/02/2015 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |