Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T14CM04729
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/30/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET TS1; PROJECT CODE REVIEW: REVISE THE TYPE OF CONSTRUCTION TO IIIB-NON SPRINKLERED. 2. SHEET TS1; PROJECT CODE REVIEW: INCLUDE UNDER 'AREA CALCULATIONS' THAT THE ALLOWABLE BUILDING AREA PER THE IBC TABLE 503 IS 19,000 SF, THEREFORE NO FIRE WALLS ARE REQUIRED FOR BUILDING SEPARATION. 3. SHEET TS1; PROJECT CODE REVIEW: UNDER 'AREA CALCULATIONS', REMOVE THE NOTES 'SOUTH SIDE OF FIRE BARRIER WALL' AND 'NORTH SIDE OF FIRE BARRIER WALL'. 4. SHEET A1.1; FLOOR PLAN: THE NORTH WALL OF THE VITALS ROOM (134) INDICATES AN E TYPE WALL IN HALL 132. PLEASE REVISE THAT WALL TO A ONE HOUR RATED FIRE PARTITION. 5. SHEET A1.1; WALL TYPES SCHEDULE: ON BOTH WALL TYPES E AND I, REVISE THE NOTE TO THE UNDERSIDE OF THE EXISTING DECK. 6. SHEET A1.1; FLOOR PLAN: CONCERNING THE REQUIREMENTS OF SECTION 1018.6 FOR CORRIDOR CONTINUITY: WITHIN THE CHECK IN ROOM (142), THERE MUST BE VERY LIMITED COMBUSTIBLES IN THAT ROOM (NO SIGNIFICANT STORAGE FILES), OR THE ROOM WILL NEED TO BE A ONE HOUR FIRE RATED ASSEMBLY (INCLUDING THE OPENING INTO THE RECEPTION AREA). IF THAT CAN NOT BE ACCOMPLISHED, THERE MUST BE A ONE HOUR RATED WALL AND DOOR ASSEMBLY SEPARATING EXITS 100C AND 100A FROM THE RECEPTION AREA. FINALLY, OPENINGS IN THE NORTH WALL OF THE PHARMACY (KEYNOTE 29) MUST HAVE A ONE HOUR RATED ASSEMBLY. 7. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
05/05/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The architectural issues have not yet been resolved; it is impossible to review the mechanical drawings at this time. [Second Comment: The Architect has not yet resolved the fire-rating issues for this building making it impossible to review your design at this time.] [Initial comment: Numerous walls will have to be fire-rated which will in turn affect the duct penetrations. Coordinate the treatment of all penetrations of fire-rated walls with the architect. Reference: Section 607, IMC 2012.] |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/12/2015 | AROMERO4 | APPROVAL SHELF | Completed |
05/12/2015 | AROMERO4 | OUT TO CUSTOMER | Completed |