Review Details: REVISION - - 2ND

Permit Number - T14CM04729
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/16/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A1.1; FLOOR PLAN: THE BASIS FOR THE REQUIRED BUILDING SEPARATION WAS BASED ON A TYPE VB CONSTRUCTION, WHICH LIMITS THE BUILDING AREA TO 9000 SF (UNFACTORED). INVESTIGATE CLASSIFYING THE CONSTRUCTION TYPE AS IIIB, WHICH WOULD ALLOW 19,000 SF. PLEASE REVIEW.
2. SHEET A1.1; FLOOR PLAN: IF WALL TYPE T (AT HALL 179) IS REQUIRED TO BE A TWO HOUR WALL FOR AREA SEPARATION, IT WILL BE A FIRE WALL. IF IT IS REQUIRED TO BE A ONE HOUR CORRIDOR WALL, IT WILL BE A FIRE PARTITION. PLEASE REVISE THE WALL NAMES AS REQUIRED. PROVIDE A DETAIL REFERENCE.
3. SHEET A1.1; FLOOR PLAN: EXISTING WALL H (AT O.R. 113 AND ULTRASOUND 114) IS A CORRIDOR WALL AND IS REQUIRED TO BE A ONE HOUR FIRE PARTITION. IT IS REQUIRED TO EXTEND FROM THE WALL TO THE BOTTOM OF THE ROOF DECK. REVISE THE SCHEDULE.
4. SHEET A1.1; FLOOR PLAN: THE CORRIDOR AT THE JANITOR CLOSET 110, THE HAZARD ROOM 111, THE RESTROOM 109, AND THE LAB 108 ARE CORRIDOR WALLS AND ARE REQUIRED TO BE ONE HOUR FIRE PARTITIONS THAT EXTEND TO THE BOTTOM OF THE ROOF DECK. PROVIDE A DETAIL REFERENCE.
5. SHEET A1.1; FLOOR PLAN: WALL E AT HALL 115 IS A CORRIDOR WALL AND IS REQUIRED TO BE A ONE HOUR FIRE PARTITION THAT EXTENDS TO THE BOTTOM OF THE ROOF DECK. PROVIDE A DETAIL REFERENCE.
6. SHEET A1.1; FLOOR PLAN: EXISTING WALL H AT HALL 115 IS A CORRIDOR WALL AND IS REQUIRED TO BE A ONE HOUR FIRE PARTITION THAT EXTENDS TO THE BOTTOM OF THE ROOF DECK. PROVIDE A DETAIL REFERENCE.
7. SHEET A1.1; FLOOR PLAN: EXISTING WALL S IN THE SCHEDULE SHOULD INDICATE IT EXTENDS TO THE BOTTOM OF THE ROOF DECK. PLEASE ADD TO THE SCHEDULE.
8. SHEET A1.1; WALL TYPE U: INCLUDE IN THE DESCRIPTION THAT THE WALL SHOULD EXTEND TO THE BOTTOM OF THE ROOF DECK.
9. SHEET A1.1; WALL SCHEDULE: THE TYPE E WALL IS REQUIRED AT CORRIDORS TO BE A ONE HOUR RATED FIRE PARTITION EXTENDING TO THE BOTTOM OF THE ROOF DECK. PLEASE VERIFY AT ALL LOCATIONS.
10. SHEET A1.1; FLOOR PLAN: OFFICE 116 REQUIRES A RATED DOOR OR EACH WALL IN THE OFFICE MUST BE A ONE HOUR RATED FIRE PARTITION. PLEASE VERIFY.
11. SHEET A1.1; FLOOR PLAN: HALL 104 APPEARS TO BE A DEAD END CORRIDOR THAT EXCEEDS THE LENGTH REQUIREMENTS OF SECTION 1018.4. PLEASE VERIFY.
12. SHEET A1.1; WALL SCHEDULE: PLEASE VERIFY THE WINDOW AND FRAME ASSEMBLLY IN WALL U MEET THE FIRE REQUIREMENTS.
13. SHEET A1.1; FLOOR PLAN: SECTION 1018.6 INDICATES FIRE RESISTANCE RATED CORRIDORS SHALL BE CONTINUOUS TO AN EXIT. THE RECEPTION AREA 100 RECEIVES OCCUPANTS FROM TWO HALLWAYS, BUT THE CORRIDORS ARE NOT CONTINUOUS TO THE EXIT, AND THE RECEPTION AREA IS NOT LIKELY TO BE CONSTRUCTED AS REQUIRED FOR CORRIDORS. PLEASE VERIFY.
14. SHEET A1.1; FLOOR PLAN: OPEN SPACE 175 APPEARS TO HAVE ONLY ONE EXIT. PLEASE VERIFY THE ONE EXIT MEETS THE REQUIREMENTS OF TABLE 1015.1.
15. SHEET A1.1; FLOOR PLAN: PLEASE VERIFY EXIT DOORS MEET THE REQUIREMENTS OF TABLE 716.5. IT APPEARS EXIT DOORS 179A, 132A, 106B, 100A, 100B, 148B, 161A, AND 175 A MIGHT NOT MEET THOSE REQUIREMENTS.
16. SHEET A1.1; FLOOR PLAN: FLOOR PLAN KEYNOTE 15 INDICATES AN EXISTING STOREFRONT WINDOW SYSTEM AT SEVERAL EXITS. PLEASE VERIFY THE STOREFRONT ASSEMBLY FIRE RATING.
17. SHEET A1.2; DETAIL 3: THE DETAIL INDICATES A NOTE 5 AT THE GYPSUM FASTENERS. PLEASE REVISE TO NOTE 3.
18. SHEET A4.0; DOOR SCHEDULE: DOORS 112A AND 113A SHOULD HAVE 20 MINUTES UNDER 'LABEL' (REMARKS INDICATE A 20 MINUTE RATED DOOR). PLEASE REVISE.
19. SHEET A4.0; DOOR SCHEDULE: DOOR 132A SHOULD HAVE 20 MINUTES UNDER 'LABEL'. PLEASE REVISE.
20. SHEET A4.0; DOOR SCHEDULE: DOOR 114A SHOULD HAVE 20 MINUTES UNDER 'LABEL'. PLEASE REVISE.
21. GENERAL: PLEASE INCLUDE ALL DRAWINGS FOR REVIEW. INSERT UPDATED (REVISED) DRAWINGS INTO THE COMPLETE SET.
22. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/20/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Numerous walls will have to be fire-rated which will in turn affect the duct penetrations. Coordinate the treatment of all penetrations of fire-rated walls with the architect. Reference: Section 607, IMC 2012.