Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T14CM04729
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/25/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/25/2014 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 08/25/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Comment not addressed. [Initial comment: Provide structural calculations and details to show how the proposed water heater platforms shown in details 2/P2.0 and 3/P2.0 are to be safely supported from the building structure. Reference: Section 301.2, IPC 2012.] 2. Comment not addressed. [Initial comment: Verify that the use of a temperature mixing valve with the tankless water heater complies with the water heater manufacturer's listing requirements. Reference: Section 303.2, IPC 2012.] 3. Verify that the 3/4" pan drain (slope 1/4" per foot?) can accommodate the flow rate from the T&P relief valve. [Initial comment: Provide information to show that the installation of the T&P relief piping for WH-1 complies with the manufacturer's listing requirements for allowable length of the discharge pipe. Reference: Section 303.2, IPC 2012.] |