Permit Number: T14CM04729
Parcel: 13215024A

Address:
3690 S PARK AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM04729
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/25/2014 ROBERT SHERRY WATER REVIEW Completed
08/25/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. [Initial comment: Provide structural calculations and details to show how the proposed water heater platforms shown in details 2/P2.0 and 3/P2.0 are to be safely supported from the building structure. Reference: Section 301.2, IPC 2012.]
2. Comment not addressed. [Initial comment: Verify that the use of a temperature mixing valve with the tankless water heater complies with the water heater manufacturer's listing requirements. Reference: Section 303.2, IPC 2012.]
3. Verify that the 3/4" pan drain (slope 1/4" per foot?) can accommodate the flow rate from the T&P relief valve. [Initial comment: Provide information to show that the installation of the T&P relief piping for WH-1 complies with the manufacturer's listing requirements for allowable length of the discharge pipe. Reference: Section 303.2, IPC 2012.]