Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM04729
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/30/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/06/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET TS1; APPLICABLE CODES: REVISE THE ELECTRICAL CODE TO THE 2011 EDITION, AND THE ACCESSIBILITY CODE TO THE 2009 EDITION. 2. SHEET D1.0; DEMOLITION PLAN KEYNOTES: NOTES 15 AND 17 WERE NOT LOCATED ON THE PLAN. VERIFY. 3. SHEET A1.0; FLOOR PLAN: SOUTH OF THE P.T. AREA, THERE IS A REFERENCE 1/A1.3 TO AN ENLARGED RESTROOM PLAN. REVISE THE REFERENCE SHEET NUMBER. 4. SHEET A1.0; FLOOR PLAN: WEST OF THE PHARMACY THERE IS A REFERENCE 2/A1.3 TO AN ENLARGED RESTROOM PLAN. REVISE THE REFERENCE SHEET NUMBER. 5. SHEET A1.0; FLOOR PLAN: WEST OF THE BREAK ROOM THERE IS A REFERENCE 3/A1.3 TO AN ENLARGED RESTROOM PLAN. REVISE THE REFERENCE SHEET NUMBER. 6. SHEET A1.0; FLOOR PLAN: BENEATH THE PLAN TITLE IS A NOTE TO SEE A4.1 FOR MILLWORK ELEVATIONS. REVISE THE NOTE. 7. SHEET A1.0 (FLOOR PLAN); SHEET A6.0 (MILLWORK ELEVATION 6): THE PLAN INDICATES A SINK AT THIS COUNTER, WHILE THE ELEVATION DOES NOT. COORDINATE. 8. SHEET A1.1; WALL TYPES SCHEDULE (TYPE B): PROVIDE THE METAL STUD SPACING. 9. SHEET A1.1; WALL TYPES SCHEDULE (TYPES E, F, AND Q): REFERENCE IS MADE TO DETAIL 1/A2.0. REVISE THE REFERENCE. 10. SHEET A1.1; WALL TYPES SCHEDULE: WALL TYPE N WAS NOT LOCATED ON THE PLAN. VERIFY. 11. SHEET A1.1; FLOOR PLAN: GENERAL NOTE 4 INDICATES A NEW SHOWER. IS THIS TO BE USED FOR PATIENTS? IF SO, PROVIDE GRAB BAR, SEAT, AND SHOWER CONTROL DETAILS ON THE DRAWINGS PER THE ICC/ANSI SECTION 608. 12. SHEET A1.1; FLOOR PLAN GENERAL NOTES: NOTE 14 WAS NOT LOCATED ON THE PLAN. VERIFY. 13. SHEET A1.2: PROVIDE DETAILS AND/OR VERBIAGE ADDRESSING IBC SECTIONS 714 FOR FIRE BARRIER PENETRATIONS, 715 FOR FIRE RESISTANT JOINT SYSTEMS, 716 FOR FIRE BARRIER OPENINGS, AND 717 FOR FIRE BARRIER DUCT OPENINGS (INCLUDING LISTED SMOKE DAMPERS). 14. SHEET A3.0; ENLARGED PLAN 2: FLOOR PLAN KEYNOTES ARE UPSIDE DOWN. 15. SHEET A3.0; ENLARGED PLAN 3: RESTROOM ELEVATION L INDICATES A DOORWAY, WHILE THE INDICATOR ON THE PLAN DOES NOT POINT TO THE DOOR WALL. CLARIFY. 16. SHEET A6.0; MILLWORK ELEVATION 1: FINISH THIS ELEVATION, INCLULDING AN ACCESSIBLE SPACE PER THE IBC SECTION 1109. 17. SHEET A6.0; MILLWORK ELEVATION 2: PROVIDE AN ACCESSIBLE COUNTER PER THE IBC SECTION 1109. 18. SHEET A6.0; MILLWORK ELEVATION 3: PROVIDE AN ACCESSIBLE COUNTER PER THE IBC SECTION 1109. 19. SHEET A6.0; MILLWORK ELEVATION 4: PROVIDE AN ACCESSIBLE COUNTER TOP PER THE IBC SECTION 1109. 20. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 08/14/2014 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Clarify the size and the serial number of the existing water meter; Sheets P1.0 and P3.1 show different sizes and serial numbers. |
| 08/14/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide structural calculations and details to show how the proposed water heater platforms shown in details 2/P2.0 and 3/P2.0 are to be safely supported from the building structure. Reference: Section 301.2, IPC 2012. 2. Verify that the use of a temperature mixing valve with the tankless water heater complies with the water heater manufacturer's listing requirements. Reference: Section 303.2, IPC 2012. 3. Provide information to show that the installation of the T&P relief piping for WH-1 complies with the manufacturer's listing requirements for allowable length of the discharge pipe. Reference: Section 303.2, IPC 2012. 4. The drain from a pan located under a water heater (e.g. WH-1, WH-4) shall terminate either to an indirect waste receptor or to the exterior of the building. The tailpiece of a fixture is not an approved indirect waste receptor. Reference: Sections 504.7.2 and 802.3, IPC 2012. |
| 08/14/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 08/15/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed |