Review Date Reviewer's Name Type of Review Description Status Comments
07/25/2014 MICHAEL ST. PAUL ZONING REVIEW Denied P&DS TRANSMITTAL


FROM: Michael St.Paul, Planning Technician

PROJECT:
T14CM04715
3032 East 20th Street
Carport addition to SFR


TRANSMITTAL: July 25, 2014


COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).


This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). The height of the proposed carport is twelve (12) feet, six (6) inches facing the west property line. The required setback is eight (8) feet, four (4) inches. The proposed setback is four (4) feet.
07/25/2014 ANY ENGINEERING REVIEW Active
07/25/2014 MICHAEL ST. PAUL NPPO REVIEW Passed
07/25/2014 ANY BUILDING-RESIDENTIAL REVIEW Active