Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM04610
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/22/2014 | DAVID RIVERA | ZONING | REVIEW | Approved | |
07/22/2014 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
07/22/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
07/22/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A2.0; FLOOR PLAN KEYNOTES: NOTE 7 WAS NOT LOCATED ON THE PLAN. VERIFY. 2. SHEET A2.0; WALL TYPES: PROVIDE A DETAIL ON THE DRAWINGS FOR BRACING AT THE TOP OF THE WALL. INCLUDE THE BRACING SIZE AND SPACING. INCLUDE THE CONNECTION (SIZE AND QUANTITY) OF THE BRACE TO THE TOP OF THE WALL AND TO THE EXISTING STRUCTURE ABOVE. 3. SHEET S0.0; STRUCTURAL NOTES (FOUNDATIONS): NOTE 1 SHOULD INDICATE THE ALLOWABLE SOIL BEARING PRESSURE OF 1500 PSF AT 18" BELOW NATURAL GRADE. 4. SHEET S2.0; FRAMING PLAN: DETAILS C/S2.1 AND E/S2.1 ON THE SOUTH WALL SHOULD BE REVERSED. 5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
07/22/2014 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
07/23/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012. |
07/23/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify how the 1" CW will be connected to the waterless urinals. Reference: Section 303.2, IPC 2012. 2. If the shower does not have a pre-fabricated receptor, provide details to show that the construction of the receptor complies with the requirements of Section 417.5.2, IPC 2012. 3. Provide separate indirect waste pipes for each compartment of the 3-compartment sink and of the 4-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012. |
07/23/2014 | ROBERT SHERRY | WATER | REVIEW | Completed | |
07/23/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
08/29/2014 | CPIERCE1 | WWM | REVIEW | Needs Review |