Review Date Reviewer's Name Type of Review Description Status Comments
07/21/2014 MICHAEL ST. PAUL ZONING REVIEW Reqs Change P&DS TRANSMITTAL


FROM: Michael St.Paul, Planning Technician

PROJECT:
T14CM04576
5643 East 18th Street
Detached accessory structure


TRANSMITTAL: July 21, 2014


COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).


This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). The height of the wall facing the east property line on the proposed detached structure is twelve (12) feet. The required setback is eight (8) feet. The proposed setback to the east property line is three (3) feet, six (6) inches.
07/21/2014 JASON GREEN ENGINEERING REVIEW Approved
07/21/2014 MICHAEL ST. PAUL NPPO REVIEW Passed
09/09/2015 EGALLET1 BUILDING-RESIDENTIAL REVIEW Needs Review