Permit Number: T14CM04537
Parcel: 12315134A

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T14CM04537
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/18/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Reqs Change only 1 service per building is allowed unless you have met the requirements of NEC 230.2. Provide information as to why a new service would be required rather than a tap off of the existing services.