Permit Review Detail
Review Status: Active
Review Details: COMMERCIAL - TI
Permit Number - T14CM04531
Review Name: COMMERCIAL - TI
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/18/2014 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 07/18/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012. 2. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson. 3. The City of Tucson did not adopt ASHRAE Standard 62.1 for ventilation calculations and the 2012 IMC only references the ASHRAE Standard for the purpose of calculating the system ventilation efficiency (Ev). Provide calculations to show that the ventilation system is sized in accordance with Section 403.3, IMC 2012; for HVAC systems serving multiple zones, see Section 403.3.2.3, IMC 2012. |
| 07/18/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | provide automatic controls and occupancy sensors for lighting per section C405.2.2.1 and C405.2.2.2 of 2012 IECC |
| 07/18/2014 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Provide the size of the water meter and the reduced pressure backflow prevention assembly serving this building. Reference: Section 107.2.1, IBC 2012. |
| 07/18/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify structural calculations on sheet S2.1 that the truss analysis for for the new HVAC unit load spread over four joists and that this is OK. 2. Provide companion seats for accessible seating at the back of the main auditorium. END OF REVIEW |
| 07/18/2014 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 07/18/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide water supply isometrics. Reference: Section 107.2.1, IBC 2012. 2. Provide waste and vent isometrics. Reference: Section 107.2.1, IBC 2012. 3. Provide tempered water for the lavatories and public hand-washing sinks in restrooms using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012. 4. Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson. 5. Provide an approved anti-siphon device (e.g. vacuum relief valve, not a vacuum breaker) for storage-type water heaters located above any fixture outlets. Reference: Section 504.1, IPC 2012. 6. Provide cleanouts for all horizontal drains; the cleanouts shall be sized per Section 708.7, IPC 2012 and shall open to allow cleaning in the direction of flow. Reference: Sections 708.3.1 and 708.5, IPC 2012. |
| 07/18/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/18/2014 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/05/2015 | AROMERO4 | WWM | REVIEW | Completed |