Permit Number: T14CM04496
Parcel: 134270010

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T14CM04496
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/21/2014 MICHAEL ST. PAUL PLANNING-CITY HALL REVIEW Approved
07/21/2014 MICHAEL ST. PAUL ZONING REVIEW Approved
07/23/2014 MARTIN BROWN FIRE REVIEW Denied Please provide quantities on amount of electrolyte per battery, total amount of electrolyte on site, and how this quantity conforms with chapter 50 (hazardous materials) of the 2012 International Fire Code
07/24/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT: THE STRUCTURAL SET OF DRAWINGS MUST BE SUBMITTED ON FULL SIZE DRAWINGS TO MEET THE CITY OF TUCSON STANDARDS FOR LETTERING AND LEGIBILITY. INCLUDE THE SLED LOCATION ON THE ROOF PLAN, SLED MEMBER SIZES, AND DETAILS OF THE BALLAST SYSTEM.
07/25/2014 CPIERCE1 COMMUNICATIONS REVIEW Completed PER JEFFREY SELIGMAN

Final Status

Task End Date Reviewer's Name Type of Review Description
08/14/2014 FERNE RODRIGUEZ OUT TO CUSTOMER Completed