Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T14CM04496
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/21/2014 | MICHAEL ST. PAUL | PLANNING-CITY HALL | REVIEW | Approved | |
| 07/21/2014 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 07/23/2014 | MARTIN BROWN | FIRE | REVIEW | Denied | Please provide quantities on amount of electrolyte per battery, total amount of electrolyte on site, and how this quantity conforms with chapter 50 (hazardous materials) of the 2012 International Fire Code |
| 07/24/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. PREVIOUS COMMENT: THE STRUCTURAL SET OF DRAWINGS MUST BE SUBMITTED ON FULL SIZE DRAWINGS TO MEET THE CITY OF TUCSON STANDARDS FOR LETTERING AND LEGIBILITY. INCLUDE THE SLED LOCATION ON THE ROOF PLAN, SLED MEMBER SIZES, AND DETAILS OF THE BALLAST SYSTEM. |
| 07/25/2014 | CPIERCE1 | COMMUNICATIONS | REVIEW | Completed | PER JEFFREY SELIGMAN |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/14/2014 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |