Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM04465
Parcel: 10510252A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM04465
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2014 MICHAEL ST. PAUL ZONING REVIEW Approved
07/16/2014 LOREN MAKUS ENGINEERING REVIEW Approved
07/17/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
07/17/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide structural calculations for te support of the Type I hood.
2. Provide a hood for the gas-fired oven.
3. Verify that the specified evaporative cooling section of the makeup air unit is recirculating the cooling water.
07/17/2014 KEN BROUILLETTE FIRE REVIEW Approved
07/17/2014 ROBERT SHERRY WATER REVIEW Reqs Change Verify the size of the existing RP for the water service: the pressure loss calculations indicate the 2" meter is followed by a 3/4" RP.
07/17/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Coordinate the gas piping design with the kitchen equipment schedule for the gas input values and renumber the equipment tags in detail 2/P2.0.
07/23/2014 CPIERCE1 WWM REVIEW Completed
07/23/2014 CPIERCE1 BUILDING-COMMERCIAL REVIEW Needs Review
07/23/2014 CPIERCE1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review