Permit Number: T14CM04462
Parcel: 130130670

Address:
3601 E 34TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM04462
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET 3 (BUNGER DRAWINGS); STRUCTURAL CALCULATIONS (SHEET 2): THE CALCULATIONS INDICATE FOOTING F-1 HAS 6-#5 REINFORCING EACH WAY, WHILE THE DRAWINGS INDICATE 4-#5 EACH WAY TOP AND BOTTOM. CLARIFY.
2. SHEET 3 (BUNGER DRAWINGS); STRUCTURAL CALCULATIONS (SHEET 12): THE CALCULATIONS INDICATE FOOTING F-3 HAS 5-#5 REINFORCING EACH WAY, WHILE THE DRAWINGS INDICATE 4-#5 EACH WAY TOP AND BOTTOM. CLARIFY.
3. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.