Permit Number: T14CM04462
Parcel: 130130670

Address:
3601 E 34TH ST

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T14CM04462
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/22/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. BUNGER STEEL DRAWINGS; DRAWING 1: PER THE IBC SECTION 107.3.4, THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS PREPARED BY OTHERS. VERIFY THE ARCHITECT OF RECORD AND/OR STRUCTURAL ENGINEER OF RECORD HAVE REVIEWED THE BUNGER STEEL DRAWINGS AND THOSE DRAWINGS ARE IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
2. BUNGER STEEL DRAWINGS; DRAWING 3: PROVIDE THE CALCULATIONS FOR THE FOUNDATIONS.
3. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/30/2014 CPIERCE1 OUT TO CUSTOMER Completed