Permit Number: T14CM04395
Parcel: 122172380

Address:
3430 E ELIDA ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T14CM04395
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/21/2014 LOREN MAKUS ENGINEERING REVIEW Approved FUP with Elevation Certificates Required
07/30/2014 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 8-1-14
Activity: T14CM04395
Address: 3430 E. Elida
Applicant: Donald Livingstone

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code with local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Remove references to the Model Energy Code. The City of Tucson has adopted the 2012 International family of codes. As of 1/01/2013 all code references should refer to the currently adopted code or appeal must be made to the Building Official for alternate code use.

SECTIONS - DETAILS:
2. Non-bearing interior wall conditions must have gap below engineered truss systems for deflection with appropriate hardware, R802.10.1(10).

PLUMBING PLAN:
3. The IRC and UPC codes are not interchangeable. As of 1/01/2013 all code references should refer to the currently adopted code or appeal must be made to the Building Official for alternate code use.
4. Provide accurate water fixture unit values, P2903.6.
5. Specify the location of the fireplace indicated on the gas appliance schedule and provide a gas piping system sized for the proposed demand, G2413.1, Table G2413.4 (1).
6. Specify water conservation requirements: Water closets = 1.6 gallons per flush, Sinks = 2.2 gpm, Showerheads = 2.5 gpm, P2903.2.
7. Specify the size of the proposed water meter, the lowest available working pressure and the diameter of the water supply line from the meter to the service entrance, P2903.7.
8. All construction drawings submitted after June 1, 2010 for one- or two-family dwellings must provide gray water utilization or preparation, Ordinance #10579/11089 revised July 9, 2013. Provide gray water segregation for at least one (1) bathing fixture or clothes washing machine for all single story buildings when the available distribution area exceeds 200 square feet. Gravity discharge is required when feasible including all fixtures on stories above grade level.
9. Provide note requiring that water hammer arrestor be installed in accordance with ASSE 1010-2004 on water lines serving appliances equipped with quick-closing valves to include but not limited to: clothes washers, dishwashers, and refrigerators, IRC P2903.5.
10. Show the size of the vent and cleanout required at the kitchen sink, P3005.2, P3101.1..
11. Specify the location of the pressure and temperature relief valve for the water heater terminating to the exterior facing no more than 6 above the grade, P2803.6.1.

MECHANICAL PLAN:
12. Provide Manual J/S/D calculations for the forced air unit in accordance with M1401.3, M1601.1.
13. Specify the location of the return air from bedroom areas.
14. Provide a minimum 100 CFM exhaust fan for kitchen venting, R303.3, M1507.
15. Show dryer vent location for venting to exterior (max 25' w/bend reductions), M1502.

ELECTRICAL PLAN:
16. GFCI protection required for all receptacles located in garages including those located on the ceiling, E3902.

INTERNATIONAL ENERGY CONSERVATION CODE:
17. Indicate how the thermal envelope of the building will be maintained around areas with combustion air openings through the insulation, N1102.