Permit Number: T14CM04365
Parcel: 137055350

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM04365
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/03/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Rooms 103, 109, 110, 115, and 117 are still using the egress corridor as a return duct. [Second comment: The mechanical code does not differentiate between fire-rated and non-fire-rated corridors so the presence or absence of doors is not applicable. Corridors are not to be used as a means of transferring air.] [Initial comment: Revise the mechanical design as required to avoid using the corridors as return air ducts. Reference: Section 601.2, IMC 2012.]
10/03/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Four of the details on sheets P-1 and P-2 (2 details on each sheet) still have fonts smaller than 3/32". [Second comment: Comment not resolved; four of the details on sheets P-1 and P-2 and the description of the drinking fountain in the fixture schedule have fonts smaller than 3/32".] [Initial comment: Revise the font size used on the drawings to a minimum of 3/32-inch. Reference: Section 107.2.1, IBC 2012.]
10/08/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change The water heater platform specifications on sheet P1 calls for a mounting platform WHP1 and refrences detail 17/A2.1. There is no detail at reference detail block 17/A2.1 Please reconcile.