Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T14CM04365
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/04/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
09/11/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
09/16/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Please provide the water heater support detail on Sheet S1 with structural engineer's seal and signature. Also, insure structural wall analysis is completed. END OF REVIEW |
09/24/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Comment not resolved; the four of the details on sheets P-1 and P-2 and the description of the drinking fountain in the fixture schedule have fonts smaller than 3/32". [Initial comment: Revise the font size used on the drawings to a minimum of 3/32-inch. Reference: Section 107.2.1, IBC 2012.] |
09/24/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The mechanical code does not differentiate between fire-rated and non-fire-rated corridors so the presence or absence of doors is not applicable. Corridors are not to be used as a means of transferring air. [Initial comment: Revise the mechanical design as required to avoid using the corridors as return air ducts. Reference: Section 601.2, IMC 2012.] |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/25/2014 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
09/25/2014 | CPIERCE1 | REJECT SHELF | Completed |