Permit Number: T14CM04365
Parcel: 137055350

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T14CM04365
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/04/2014 MARTIN BROWN FIRE REVIEW Approved
09/11/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
09/16/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change Please provide the water heater support detail on Sheet S1 with structural engineer's seal and signature. Also, insure structural wall analysis is completed.
END OF REVIEW
09/24/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Comment not resolved; the four of the details on sheets P-1 and P-2 and the description of the drinking fountain in the fixture schedule have fonts smaller than 3/32". [Initial comment: Revise the font size used on the drawings to a minimum of 3/32-inch. Reference: Section 107.2.1, IBC 2012.]
09/24/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The mechanical code does not differentiate between fire-rated and non-fire-rated corridors so the presence or absence of doors is not applicable. Corridors are not to be used as a means of transferring air. [Initial comment: Revise the mechanical design as required to avoid using the corridors as return air ducts. Reference: Section 601.2, IMC 2012.]

Final Status

Task End Date Reviewer's Name Type of Review Description
09/25/2014 SHANAE POWELL OUT TO CUSTOMER Completed
09/25/2014 CPIERCE1 REJECT SHELF Completed