Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM04352
Parcel: 11504520B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM04352
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/18/2014 MARTIN BROWN FIRE REVIEW Denied Door hardware schedule (sheet A2) does not appear to meet the requirements of section 1008.1.10 of the 2012 International Fire Code or International Building Code. Please review and revise.
07/24/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change GENERAL
1. Several sheets have non compliant lettering size. COT Standard is 3/32" actual height, minimum for both upper and lower case. Please revise all sheets and resubmit
SHEET A1
2. Project Data: Occupancy type A3, change to A2 restaurant.
3. At detail 1, Change the "ADA" title to "Accessible".
4. Door 3 accessible clearance (corridor width) is not compliant to ICC A117.1, Section 404.2.3.2, and figure (g). Corridor needs to be 4' wide.
5. Provide a panic bar at door 2 as required by the 2012 IBC, Section 1008.1.10.
6. Change all elevation references at the Cashier Counter to "A1".
SHEET A2
7. How is Sushi Conveyer supported? Please provide details for review prior to installation.
SHEET A3
8. Provide structural calculations and details for:
a. The exhaust hood support.
b. The Polution Control Unit and show details of mounting height for all it's elements including exhaust outlet outside of the building.
9. Provide structural calculations for the clay tile Bar Soffit.
10. Show accessible seating as required by the 2012 IBC, Section 1109.11 and the 2009 ICC A117.1, Section 902.
a. This includes all bar counters.
END OF REVIEW
07/25/2014 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed Fees paid
08/08/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify the type of water heater to be installed; the food service equipment schedule on sheet A4 calls for a 75-gallon gas-fired unit. Reference: Section 107.2.1, IBC 2012.
2. Revise the water heater detail (sheet MPS) to show how the recirculating hot water system is to be installed. Reference: Section 107.2.1, IBC 2012.
3. Table 402.4 (5) is cited as the method used to determine the size of the 2 PSIG main gas supply. Are additional future gas loads being considered or was the pipe size actually determined with Table 402.4 (3)? Reference: Section 402.1, IFGC 2012.
4. Provide material standards for all plumbing fixtures being provided by others. Reference: Sections 303.4 and 402, IPC 2012.
5. Provide tempered water for the lavatories and public hand-washing sinks in restrooms using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
6. Hand sinks in the kitchen are allowed to connect to the sanitary waste system instead of the grease waste system only if each sink has a sign posted above it stating, "HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED." Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson.
7. Clarify why the sizing calculations for the gravity grease interceptor shown in Section 1003.3, IPC 2012 (C), as amended by the City of Tucson were not used. An over-sized gravity grease interceptor can result in corrosive conditions within the interceptor and odor problems outside of the interceptor.
08/11/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide structural calculations and details to show how the fan coil units are to be connected to the building structure. Reference: Section 302.1, IMC 2012.
2. Provide structural calculations and details to show how exhaust fan EF-1 is to be connected to the building structure. Reference: Section 302.1, IMC 2012.
3. Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2012 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2012.
4. Provide make up air from outside of the building (e.g. not from within the enclosed parking area). Reference: Sections 202 and 403.2, IMC 2012.
5. Show that the outlet of fan EF-2 complies with the requirements of Section 501.3.1 (3), IMC 2012.
6. Show that the outlet of fan EF-1 complies with the requirements of Sections 506.3.13.2 and 506.3.13.3, IMC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/19/2014 AROMERO4 APPROVAL SHELF Completed
08/19/2014 AROMERO4 OUT TO CUSTOMER Completed
08/19/2014 CPIERCE1 REJECT SHELF Completed