Permit Number: T14CM04352
Parcel: 11504520B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM04352
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2014 STEVE SHIELDS ZONING REVIEW Approved
07/11/2014 JASON GREEN ENGINEERING REVIEW Approved
07/11/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Change Occupancy Classification from A3 to A2.
2. Finish code analysis:
a. Required number of exits
b. Toilet fixture calculation
3. Provide structural calculations and details for:
a. Interior clay tile overhang
b. Range Exhaust hood supports
c. All suspended HVAC supports
END OF REVIEW
07/11/2014 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
07/14/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
07/14/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
07/14/2014 ROBERT SHERRY WATER REVIEW Completed
07/14/2014 KEN BROUILLETTE FIRE REVIEW Denied NEED PANIC HARDWARE ON SECOND EXIT
07/14/2014 SPOWELL1 WWM REVIEW Needs Review
07/14/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review