Permit Number: T14CM04331
Parcel: 11304447B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM04331
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/17/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
07/18/2014 MARTIN BROWN FIRE REVIEW Approved
07/22/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change 1. Please provide structural details and calculations for the following:
a. All new roof top mounted HVAC equipment.
b. All new light pole foundations.
END OF REVIEW
07/28/2014 ROBERT SHERRY WATER REVIEW Completed
07/28/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves (e.g. P1 and P2). Reference: Section 604.9, IPC 2012.
2. Verify the dimensions of the water heater closet and its door. The closet appears to be about 24" wide but is scheduled to have a 3'-0" door (door #204). Show how the specified water heater will be able to be maintained or replaced in the proposed water heater closet. Reference: Sections 501.4 and 502.5, IPC 2012.
07/28/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.
2. Revise the mechanical design as required to avoid using the corridor as a return air duct (see HP-3 and HP-7). Reference: Section 601.2, IMC 2012.