Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T14CM04297
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/10/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Needs Review | State approved building |
| 07/10/2014 | LAITH ALSHAMI | ENGINEERING | REVIEW | Approved | |
| 07/10/2014 | RONALD BROWN | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 07/10/2014 | SPOWELL1 | COMMUNICATIONS | REVIEW | Needs Review | |
| 07/10/2014 | MARTIN BROWN | FIRE | REVIEW | Denied | Please calculate number of batteries, quantity of electrolyte per battery, and total amount of electrolyte. Indicate how this quantity is below the maximum allowable quantity per 2012 International Fire Code, chapter 50. |
| 07/10/2014 | STEVE SHIELDS | ZONING | REVIEW | Needs Review | |
| 07/10/2014 | SPOWELL1 | PLANNING-CITY HALL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/10/2014 | SHANAE POWELL | OUT TO CUSTOMER | Completed |