Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T14CM04269
Parcel: 10510252A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM04269
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2014 MICHAEL ST. PAUL ZONING REVIEW Approved
07/16/2014 LOREN MAKUS ENGINEERING REVIEW Approved
07/16/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A2; KEYNOTES: PROVIDE CLEARANCE DIMENSIONS IN NOTE 1.
2. SHEET A2; KEYNOTES: NOTE 1 WAS NOT LOCATED ON THE PLAN. VERIFY.
3. SHEET A2; KEYNOTES: PROVIDE THE DETAIL REFERENCE IN NOTE 7.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
07/16/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
07/17/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide cooling/heating load calculations.
07/17/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Reqs Change Wall type W-03 is insufficient for mounting transformer brackets capable of supporting transformers 1,2,3 (along line 2). Provide alternate support method.
07/17/2014 ROBERT SHERRY WATER REVIEW Completed
07/17/2014 KEN BROUILLETTE FIRE REVIEW Approved
07/17/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide accessible drinking fountains or a hi-low drinking fountain.
2. Provide structural calculations for the attachment of the water heater platform to the building structure.
3. Show how the proposed reduced pressure backflow preventer will be accessible for maintenance.
07/21/2014 SPOWELL1 WWM REVIEW Needs Review