Permit Number: T14CM04156
Parcel: 13316020P

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM04156
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT 12; SHEET S1.0; GENERAL STRUCTURAL NOTES: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE.
2. SHEET S2.0: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE DETAIL NOTES.
3. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
08/22/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Comment not resolved; each compartment of the 3-compartment sink shall be separately drained. Today's wash compartment may be tomorrow's sanitizing compartment. [Initial comment: Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.]
08/22/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/26/2014 AROMERO4 APPROVAL SHELF Completed
08/26/2014 AROMERO4 OUT TO CUSTOMER Completed
08/26/2014 CPIERCE1 REJECT SHELF Completed