Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM04156
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/10/2014 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 07/18/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET PD; FIRE SPRINKLERS: REVISE THE AUTOMATIC FIRE SPRINKLER SYSTEM IBC SECTION REFERENCE FROM 900 TO 903. 2. SHEET PD; EXITING: REVISE THE EXIT REQUIREMENTS IBC SECTION REFERENCE FROM 1015.1 TO 1005.3.2. 3. SHEET A1.0; KEY NOTES (10): REFERENCE DETAIL 101 ON SHEET S20 FOR THE WATER HEATER SUPPORT ABOVE THE MOP SINK. 4. SHEET A1.0; KEY NOTES: NOTE 16 REFERENCED TO A TABLE NEAR THE ENTRY DOOR IS INCORRECT. REVISE. 5. SHEET A1.0; FLOOR PLAN: REFERENCE DETAILS 04 AND 05 ON SHEET S1.0 FOR THE GRILL AND BREAD OVEN HOOD SUPPORTS. 6. SHEET A2.0; KEY NOTES: NOTE 10 WAS NOT LOCATED ON THE PLAN. VERIFY. 7. SHEET A5.0; ELEVATIONS 3D AND 4A: PER THE ICC/ANSI SECTION 604.7, THE TOILET PAPER DISPENSER SHALL BE LOCATED WITHIN AN AREA 24" MINIMUM AND 42" MAXIMUM FROM THE REAR WALL. REVISE THE ELEVATIONS TO MEET THAT REQUIREMENT. 8. SHEET A5.0; DETAIL 5 (TOILET ELEVATION-SIDE): PER THE ICC/ANSI SECTION 604.7, THE TOILET PAPER DISPENSER SHALL BE LOCATED WITHIN AN AREA 24" MINIMUM AND 42" MAXIMUM FROM THE REAR WALL. REVISE THE ELEVATION TO MEET THAT REQUIREMENT. 9. SHEET A5.0; DETAIL 5 (TOILET ELEVATION-SIDE): PER THE ICC/ANSI SECTION 604.5.1, THE VERTICAL GRAB BAR SHALL BE LOCATED 39" TO 41" FROM THE REAR WALL. REVISE THE ELEVATIONS TO MEET THAT REQUIREMENT. 10. SHEET A5.0; DETAIL 5 (TOILET ELEVATION-FRONT): PER THE ICC/ANSI FIGURE 604.5.2, THE HORIZONTAL GRAB BAR SHALL EXTEND A MINIMUM 12" FROM THE CENTERLINE OF THE TOILET TOWARD THE SIDE WALL. REVISE THE ELEVATION TO MEET THAT REQUIREMENT. 11. SHEET A5.0; DETAIL 5 (TOILET ELEVATION-FRONT): PER THE ICC/ANSI SECTION 604.2(a), CENTERLINE OF THE TOILET SHALL BE LOCATED 16" MINIMUM TO 18" MAXIMUM FROM THE SIDE WALL. REVISE THE ELEVATION TO MEET THAT REQUIREMENT. 12. SHEET S1.0; GENERAL STRUCTURAL NOTES: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE. 13. SHEET S1.0; DETAIL 03: IS NOTE 3 CORRECT? VERIFY. 14. SHEET S20; DETAIL 106: EXTEND THE ARROW ON NOTE 1. 15. SHEET S20; DETAIL 107: REVERSE NOTES 2 AND 3. 16. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 07/18/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment serving this suite. Reference: Sections C403.2.1 and C403.2.2, IECC 2012. 2. Show that the controls for the existing HVAC systems meet the requirements of Sections C403.2.4 and C403.3. Reference: Section C303.1, International Energy Conservation Code 2012. 3. Show the size, routing, and termination of the condensate drains from E1 and E2. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson. 4. Provide the structural detail showing how the hood supports are to be attached to the building structure in accordance with Section 507.6, IMC 2012 (the hood hanging weight plus the weight of personnel working in or on the hood) as noted in detail 3/M2.0. Reference: Section 302.1, IMC 2012. 5. Revise the balancing data for the restroom exhaust fans as shown in the exhaust fan schedule so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2012. |
| 07/18/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The two packaged rooftop units are gas-fired. Unless the kitchen appliances are served by a separate gas meter, provide a diagram of the complete natural gas distribution system showing the all of the loads, developed lengths, and the layout of the distribution piping. Reference: Section 107.2.1, IBC 2012. 2. Provide structural calculations and mounting details for the mounting shelf for the water heater to show that the water heater will be safely supported from the building structure. Reference: Section 301.2, IPC 2012. 3. Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. (Note that the specified faucet has been discontinued by the manufacturer.) Reference: Section 416.6, IPC 2012, as amended by the City of Tucson. 4. Appliances (e.g. tea brewers, ice makers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012. 5. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012. |
| 07/18/2014 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/24/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 07/24/2014 | LAITH ALSHAMI | ENGINEERING | REVIEW | Approved | |
| 07/25/2014 | DAVID RIVERA | ZONING | REVIEW | Approved |