Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T14CM04144
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/23/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEETS A-1.1 AND A-1.2; KEYNOTES: NOTES 10, 12, AND 15 WERE NOT LOCATED ON THE PLANS. VERIFY. 2. SHEET A-2.1; ELEVATION 1 AND SECTION 2: PROVIDE THE RAIL DIMENSIONS AS REQUIRED BY THE IBC SECTION 1013 (TOP OF TOP RAIL AND BOTTOM OF BOTTOM RAIL ABOVE THE EXISTING WALKWAY. 3. SHEET S2.0; PLANS: THE KEYNOTE REFERENCE NUMBERS AND SECTION REFERENCES ARE NOT LEGIBLE. REVISE. 4. SHEET S4.0 (DETAIL 206); STRUCTURAL CALCULATIONS (SHEET 12): THE CALCULATION CONFIGURATION INDICATES THE ANGLE IS LONG LEG VERTICAL, WHILE THE DETAIL INDICATES THE SHORT LEG VERTICAL. CLARIFY. 5. SHEET S4.0; DETAIL 202: NOTE 10 WAS NOT LOCATED ON THE DETAIL. VERIFY. 6. STRUCTURAL CALCULATIONS; SHEETS 4 AND 5: EVEN THOUGH THE CALCULATIONS FOR BUILDINGS "O" AND "P" ARE THE SAME AS BUILDINGS "M" AND "N", REVISE THE PLAN TITLES IN THE CALCULATIONS TO BUILDINGS "O" AND "P". 7. STRUCTURAL CALCULATIONS; SHEET 6: CHANGE BEAMS B1 AND B2 SO THEY REFERENCE BUILDINGS "O" OR "P". 8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/30/2014 | CPIERCE1 | REJECT SHELF | Completed |