Permit Number: T14CM04139
Parcel: 13316020P

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T14CM04139
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/08/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
08/08/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
08/11/2014 ROBERT SHERRY WATER REVIEW Reqs Change Provide an appeal to the building official for approval of the use of a balancing valve and an expansion tank to emulate the demand of a flush tank system as an alternative engineered design. Reference: Section 316.1, IPC 2012. [Initial comment: This suite is served by a 1" water meter and Tucson Water limits a 1" water meter to a maximum demand of 37.5 GPM. The water service demand appears to be far in excess of 37.5 GPM. Evaluate the water demand and make the appropriate modifications to either reduce the demand or increase the size of the meter.]
08/11/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide an appeal to the building official for approval of the use of a balancing valve and an expansion tank to emulate the demand of a flush tank system as an alternative engineered design. Reference: Section 316.1, IPC 2012. [Initial comment: Verify that the water in the service pipe will not exceed 8 FPS for the calculated water demand. Include all fixtures and water-connected appliances when calculating the total demand and determining pipe sizes. Reference: Sections 303.2 and 604.3, IPC 2012.]
08/11/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed