Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM04054
Parcel: 123120650

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T14CM04054
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/23/2014 RAFAEL CANCINO BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS

Date: July 23, 2014
Activity: T14CM04054
Address: 1001 E. Seneca St.
Applicant: TED


Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide revised plans and calculations, highlighting any changes or with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2012 IRC with amendments on 1/1/2012. Show the code references on the plans.

GENERAL NOTES:

" Limit all code references to those recognized by the City of Tucson. Adopted 2012 codes are listed at the Planning & Development Services web site. Show the code references used for the design.
" Please make spelling corrections to sheet A1.1.


SITE PLAN:

1. Please provide information on water meter size and ensure it is of sufficient size to handle four bathrooms, and/or information on multiple meters.

FOUNDATION PLAN:

1. Provide foundation plan for new additions.

FLOOR PLAN:

1. Ensure required clearances are available in bathrooms.

FRAMING PLAN:

1. Please provide framing plans for new additions and denote shearwall locations.

SECTIONS PLAN:

1. Provide structural details and sections.

MECHANICAL/PLUMBING/ELECTRICAL PLAN:

1. Provide mechanical, plumbing and electrical plans for new additions.


If you have any questions please contact:

Rafael Cancino
(520) 909-4891
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/20/2014 CPIERCE1 REJECT SHELF Completed