Permit Number: T14CM03970
Parcel: 11012094D

Address:
5301 E GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM03970
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2014 KEN BROUILLETTE FIRE REVIEW Approved
08/06/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
08/19/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/19/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The submitted ventilation calculations are based on ASHRAE 62.1-2007 which is not the current code and has not been adopted by the City of Tucson. Section C403.2.5, IECC 2012 requires the capability of reducing the ventilation of a space to the minimum required ventilation supply as calculated using Section 403.3, IMC 2012. Revise the ventilation calculations so that the minimum required ventilation supply will be known. [Initial comment: Provide calculations demonstrating adequate ventilation using the current code. Reference: Section 403.2, IMC 2012.]