| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/04/2014 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 08/06/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/19/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 08/19/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The submitted ventilation calculations are based on ASHRAE 62.1-2007 which is not the current code and has not been adopted by the City of Tucson. Section C403.2.5, IECC 2012 requires the capability of reducing the ventilation of a space to the minimum required ventilation supply as calculated using Section 403.3, IMC 2012. Revise the ventilation calculations so that the minimum required ventilation supply will be known. [Initial comment: Provide calculations demonstrating adequate ventilation using the current code. Reference: Section 403.2, IMC 2012.] |