Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T14CM03970
Parcel: 11012094D

Address:
5301 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM03970
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/08/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide automatic faucets for the lavatories located in restrooms, dispensing a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson.
2. Provide tempered water for the lavatories located in restrooms using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
3. Appliances (e.g. ice makers) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012.
4. Water supply connections to beverage dispensers such as coffee makers shall be protected with backflow preventers conforming to ASSE 1022. The specified double-check vacuum breaker does not meet this requirement. Reference: Section 608.16.1, IPC 2012.
07/08/2014 ROBERT SHERRY WATER REVIEW Completed
07/08/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide calculations demonstrating adequate ventilation using the current code. Reference: Section 403.2, IMC 2012.
07/08/2014 MARTIN BROWN FIRE REVIEW Reqs Change WAITING FOR RESUBMITTAL WITH FSD LOCATIONS
07/11/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change GENERAL
1. City of Tucson document lettering standards are 3/32" minimum in actuat height for both upper and lower case lettering. Please revise all drawings that do not meet this standard and resubmit.
SHEET G-002
2. Note 5: Substitute 2012 IBC, Chapter 11 for your reference to 2006 MBC, Section 1110.
SHEET G-003
3. At the Codes and Regulations summary, please substitute the 2009 ICC A117.1 for your reference to 2003 ANSI 117.1.
SHEET A-113
3. Where are the public toilet facilities?
4. Where are the public water dispensers?
5. At detail "J2" the lavatory must be 2'-10" a.f.f.
6. Where are the elevations of the receptionest counter?
END OF REVIEW
07/11/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
07/31/2014 SHANAE POWELL OUT TO CUSTOMER Completed
07/31/2014 CPIERCE1 REJECT SHELF Completed