Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM03970
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/08/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide automatic faucets for the lavatories located in restrooms, dispensing a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson. 2. Provide tempered water for the lavatories located in restrooms using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012. 3. Appliances (e.g. ice makers) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012. 4. Water supply connections to beverage dispensers such as coffee makers shall be protected with backflow preventers conforming to ASSE 1022. The specified double-check vacuum breaker does not meet this requirement. Reference: Section 608.16.1, IPC 2012. |
07/08/2014 | ROBERT SHERRY | WATER | REVIEW | Completed | |
07/08/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide calculations demonstrating adequate ventilation using the current code. Reference: Section 403.2, IMC 2012. |
07/08/2014 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | WAITING FOR RESUBMITTAL WITH FSD LOCATIONS |
07/11/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | GENERAL 1. City of Tucson document lettering standards are 3/32" minimum in actuat height for both upper and lower case lettering. Please revise all drawings that do not meet this standard and resubmit. SHEET G-002 2. Note 5: Substitute 2012 IBC, Chapter 11 for your reference to 2006 MBC, Section 1110. SHEET G-003 3. At the Codes and Regulations summary, please substitute the 2009 ICC A117.1 for your reference to 2003 ANSI 117.1. SHEET A-113 3. Where are the public toilet facilities? 4. Where are the public water dispensers? 5. At detail "J2" the lavatory must be 2'-10" a.f.f. 6. Where are the elevations of the receptionest counter? END OF REVIEW |
07/11/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/31/2014 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
07/31/2014 | CPIERCE1 | REJECT SHELF | Completed |