Permit Number: T14CM03855
Parcel: 11202033P

Address:
2000 E ROGER RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM03855
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/23/2014 STEVE SHIELDS ZONING REVIEW Approved
06/23/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide the heating/cooling load calculations to justify the capacity of the new heat pump.
06/23/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
06/23/2014 ROBERT SHERRY WATER REVIEW Approved
06/23/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET TS1; PROJECT CODE REVIEW: REVISE THE OCCUPANCY GROUP TO THE 2012 IBC CLASSIFICATION.
2. SHEET TS1; PROJECT CODE REVIEW (OCCUPANCY LOADS): REVISE THE SF/OCCUPANT USED (85) ON THIS DRAWING TO THE IBC TABLE 1004.1.2 REQUIREMENT.
3. SHEET A1.0; FLOOR PLAN (KEYNOTES): INCLUDE IN NOTE 11 (OR ADD A DETAIL) THAT THE NEW COUNTER SHALL BE 2'-10" ABOVE FINISH FLOOR.
4. SHEET A1.0; FLOOR PLAN: THE MOVIE THEATER ROOM REQUIRES 2 EXITS WITH PROPER SEPARATION PER SECTION 1015.2.1.
5. SHEET A3.0; KEYNOTES: SEVERAL KEYNOTES ARE MISSING FROM THE ELEVATIONS. VERIFY.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/23/2014 RSHERRY1 WWM REVIEW Passed No wastewater plumbing.
06/23/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
06/23/2014 LOREN MAKUS ENGINEERING REVIEW Approved
06/23/2014 KEN BROUILLETTE FIRE REVIEW Reqs Change PLEASE UPDATE WITH CORRECT OCCUPANCY CLASSIFICATION AND THE CORRECT OCCUPANT LOAD FACTOR FOR THE LOUNGE AREA
06/23/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed