Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM03854
Parcel: 116022470

Address:
1341 N ECHO PL

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM03854
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/18/2014 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 7-18-14
Activity: T14CM03854 2nd review
Address: 1341 N Echo Pl
Applicant: Inai Maldonado

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code with local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

FLOOR PLAN:
1. Identify which windows that have safety glazing, R308.4. Note: Glazing within 60" of bathtubs or showers shall be considered hazardous locations unless located greater than 60" above the standing surface.

PLUMBING PLAN:
2. Provide a cut sheet for the proposed tankless water heater that supports the proposed gas input demand. Note: Typical on demand systems of this nature will have a peak demand near 180k Btu/h.
3. Sewer piping may not be reduced in diameter in the direction of flow, P3002.3.1. Note: The plumbing system is shown as having a 4" building drain that connects to a 3" HCS.
4. Provide note requiring that water hammer arrestor be installed in accordance with ASSE 1010-2004 on water lines serving appliances equipped with quick-closing valves to include but not limited to: clothes washers, dishwashers, and refrigerators, IRC P2903.5. Note: Clothes washing machines are not the only appliance this section applies to.

MECHANICAL PLAN:
5. Provide Manual D calculations for the forced air unit in accordance with M1401.3, M1601.1. Note: the calculations must match the layout.
6. Indicate the location and size of combustion air openings, M1701.1. Note: The gas fired appliance located in the garage will require combustion air openings.

OUTDOOR LIGHTING CODE
7. Provide cut sheets for all FCO fixtures showing the angle of cutoff, light emissions and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style).

INTERNATIONAL ENERGY CONSERVATION CODE:
8. Specify a "U" factor and solar heat gain coefficient of the windows and doors that meets or exceeds the requirements of N1102.1. The simplified prescribed energy value for climate zone 2B glazing is U=0.40 and skylights is U=0.65, the default SHGC is 0.25. Note: Sheet 5 specifies glazing values above the maximum allowable U-factor and the solar heat gain coefficient is not specified.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Clayton.Trevillyan@tucsonaz.gov
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/22/2014 SHANAE POWELL OUT TO CUSTOMER Completed
07/22/2014 CPIERCE1 REJECT SHELF Completed